Herunterladen Inhalt Inhalt Diese Seite drucken

Operating Instructions - Wilo Stratos GIGA Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Stratos GIGA:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

8.5.3 Display error page
Fig. 32: Error page (status in the event of
an error)
8.5.4 Menu groups
Basic menu
Info menu
Service menu
Error acknowledgement menu
Access disable menu
8.6

Operating instructions

8.6.1 Adjusting the setpoint
12.3
Fig. 33: Entering the setpoint
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
E000
E.025
• Settings in service mode should only be made during commission-
• Only acknowledge errors after they have been remedied.
• Only have faults remedied by qualified personnel.
• If in doubt, consult the manufacturer.
1.0.0.0
• Turn the operating button.
2200
RPM
• To confirm the change, press the operating button.
1.0.0.0
1800
RPM
If an error occurs, the error page will be shown on the display rather
than the status page. The value display shows the letter "E" and the
three-digit error code separated by a decimal point (Fig. 32).
Basic settings are shown in the main menus <1.0.0.0>, <2.0.0.0> and
<3.0.0.0>, which provide access to set values that may have to be
changed during regular pump operation.
The main menu <4.0.0.0> and its sub-menu elements show measur-
ing data, device data, operating data and current states.
The main menu <5.0.0.0> and its sub-menu elements provide access
to basic system settings for commissioning. The sub-elements are in
a write-protected mode as long as service mode is not activated.
CAUTION! Risk of material damage!
Incorrect setting changes can lead to pump operation errors, which
can lead to pump or system damage.
ing and only by qualified personnel.
In the event of a fault, the error page is displayed instead of the status
page. Pressing the operating button from this position opens the error
acknowledgement menu (menu number <6.0.0.0>). Any fault signals
present can be acknowledged after a waiting period.
CAUTION! Risk of material damage!
Errors that are acknowledged without their cause having been
remedied can result in repeated faults, which could lead to pump or
system damage.
For additional information, see chapter 11 "Faults, causes and reme-
dies" on page 119 and the error table shown there.
The main menu <7.0.0.0> is only displayed when DIP switch 2 is
in the "ON" position. It cannot be reached via normal navigation.
In the "Access disable" menu, the access disable can be activated or
deactivated by turning the operating button. The change is confirmed
by pressing the operating button.
On the status page of the display, the setpoint can be adjusted as fol-
lows (Fig. 33):
The display changes to menu number <1.0.0.0>. The setpoint begins
to flash and is increased or decreased by continuing to turn.
The new setpoint will be accepted and the display will return to the
status page.
(11-22kW)
English
99

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Stratos giga-dStratos giga b

Inhaltsverzeichnis