No.
Designation
1.0.0.0
Setpoint
2.0.0.0
Control mode
2.3.2.0
Δp-v gradient
3.0.0.0
Pump on/off
4.0.0.0
Information
4.1.0.0
Actual values
4.1.1.0
Actual values
sensor (In1)
4.1.3.0
Power
4.2.0.0
Operating data
4.2.1.0
Operating hours
4.2.2.0
Consumption
4.2.3.0
Countdown, pump
cycling
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
NOTICE:
A few elements are hidden under certain conditions and are therefore
skipped in the menu navigation.
If, for example, the external setpoint adjustment under menu
number <5.4.1.0> is set to "OFF", the number <5.4.2.0> will be
hidden. Menu number <5.4.2.0> will only be visible if menu number
<5.4.1.0> has been set to "ON".
Type
Symbol Values/explanations
±
Setting/display of the setpoint
(for further information, see
chapter 8.6.1 "Adjusting the
setpoint" on page 99)
±
Setting/display of the control
mode
(for further information, see
chapters 6.2 "Control modes" on
page 78 and 9.4 "Setting the
control mode" on page 111)
Constant speed control
Constant Δp-c control
Variable Δp-v control
PID-Control
Setting the gradient of Δp-v
(value in %)
±
ON
Pump switched on
OFF
Pump switched off
Information menus
Display of current actual values
Depending on current control
mode.
Δp-c, Δp-v: Value H in m
PID-Control: Value in %
Current power input P
Display of operating data
Sum of the pump's active hours
of operation
(counter can be reset by infrared
interface)
Energy consumption in kWh/
MWh
Time to pump cycling in h
(at a resolution of 0.1 h)
(11-22kW)
Display conditions
Not displayed for all pump
types
Not displayed for constant
speed
in W
1
The operating data refers to
the electronic module
currently being operated
Shown only for double pump
master and internal pump
cycling. Can be set in the
service menu <5.1.3.0>