Fig. 48: Acknowledging error type A or D
11.3.2 Error type B
5
8
Fig. 49: Error type B, flowchart
Incidence X < Y
6.0.0.0
E000
6.0.0.0
3/6
Fig. 50: Acknowledging error type B (X < Y)
124
60
S
0
12.3
S
1
2
3
4
6
7
75
12.3
S
If type A or D errors occur, proceed as follows to acknowledge
(Fig. 48):
• To change to the menu mode, press the operating button.
Menu number <6.0.0.0> flashes on the display.
• Press the operating button again.
Menu number <6.0.0.0> appears steady on the display.
The time remaining until the error can be acknowledged is displayed.
• Wait until the remaining time is up.
The time until manual acknowledgement is always 60 seconds for
error types A and D.
• Press the operating button again.
The error is acknowledged, and the status page is displayed.
Error type B (Fig. 49):
Program step/
Contents
query
1
• Error code is displayed
• Motor Off
• Red LED On
2
Error counter is incremented
3
Error counter > 5?
4
SSM is activated
5
> 5 min?
6
> 5 min?
7
Error acknowledged?
8
End; auto control resumes
Yes
No
If type B errors occur, proceed as follows to acknowledge:
• To change to the menu mode, press the operating button.
Menu number <6.0.0.0> flashes on the display.
• Press the operating button again.
Menu number <6.0.0.0> appears steady on the display.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format "x/y".
If the current incidence of the error is less than the maximum
incidence (Fig. 50):
• Wait for auto reset time.
On the value display, the remaining time until auto reset of the error
is displayed in seconds.
After the auto reset time has run out, the error will be automatically
acknowledged and the status page will be displayed.
NOTICE:
The auto reset time can be set on menu number <5.6.3.0>
(time input 10 to 300 s).
WILO SE 03/2018