Component
Coupling
Control terminals
Power terminals
Earth terminals
Electronic module
Module cover
Union nuts
Cable bushings
Table 10: Screw tightening torques
10.2.2 Replacing the motor/drive
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
Fig./Item
Threaded
Screw (nut)
M6-10.9
M8-10.9
Fig. 6/Item 1.41
M10-10.9
M12-10.9
M14-10.9
Fig. 9/Item 4
-
Fig. 9/Item 7
-
Fig. 2
-
Fig. 6/Item 11
M5
Fig. 3
M6
M12x1.5
M16x1.5
Fig. 2
M20x1.5
M25x1.5
DANGER! Risk of fatal injury!
There is a risk of fatal injury from electric shock when working on
electrical devices. Following removal of the electronic module, a
potentially fatal shock voltage may be present at the motor con-
tacts.
• Ensure system is voltage-free, cover or screen off adjacent live
parts.
DANGER! Risk of fatal injury!
If the rotor is driven by the impeller when the pump is at a stand-
still, dangerous contact voltage can arise at the motor contacts.
• Close the shut-off devices upstream and downstream of the pump.
• Separate the motor shaft from the coupling unit by loosening the
coupling screws.
NOTICE:
The magnets inside the motor pose no risk to persons with pacemak-
ers provided that the motor is not opened and the rotor is not
removed. The motor/drive can be replaced without any risk.
• Carry out steps 1 to 10 to dismantle the motor/drive in accordance
with chapter 10.2 "Maintenance tasks" on page 114.
NOTICE:
To dismantle and assemble the electronic module, observe the
enclosed instructions on the spare part.
• When installing the motor, follow steps 25 and 31 in
chapter 10.2 "Maintenance tasks" on page 114.
NOTICE:
Observe the specified screw tightening torque appropriate for the
thread type (see Table 10 „Screw tightening torques" on page 116).
NOTICE:
Increased bearing noises and unusual vibrations indicate bearing
wear. Then the bearing has to be changed by Wilo customer service.
Tightening torque
Nm ± 10 %
(if not otherwise
specified)
12
30
60
100
170
0.5
1.3
0.5
4.0
4.3
3.0
6.0
8.0
11.0
(11-22kW)
English
Installation
information
• Slightly oil the
sliding surfaces
• Tighten the screws
evenly
• Keep the gap even
on both sides
M12x1.5 is reserved
for the serial sensor
connection cable