c. L
P.
Minimum power limit for cooling (not available for
PV
0. 0
heating/cooling double action
SV
[0.0 ... 100.0] %
Manual Reset
S r t
PV
0
[-999 ... +999] scale points
SV
Reset power
P. S
r
PV
0. 0
[-100.0 ... +100.0] %
SV
Antireset
A. S
r
PV
0
[0 ... 9999] scale points
SV
Feedforward
F d
F
PV
0. 0
[-100.0 ... +100.0] %
SV
Softstart time
S F
o
PV
0. 0
[0.0 ... 500.0] min
SV
Alarm 1 hysteresis
KY. i
PV
- 1
[±999] scale points
SV
Alarm 2 hysteresis
K 2
Y.
PV
[±999] scale points
- 1
SV
Alarm 3 hysteresis
K 3
Y.
PV
[±999] scale points
- 1
SV
Waiting time for HB alarm intervention
K t
b.
PV
[0 ... 999] sec.
30
SV
Waiting time for LBA alarm intervention
L t
b.
PV
[0.0 ... 500.0] min.
0
SV
Power limit for LBA alarm condition
L P
b.
PV
[-100.0 ... +100.0] %.
25. 0
SV
Power output in fault condition
F P
A.
(when probe is faulty)
PV
0. 0
SV
[-100.0 ... +100.0] % ON / OFF
Set gradient (see "Application Notes"
paragraph)
G. P
S
PV
0. 0
[0.0 ... 999.9] digits/min
SV
By adding +32 to the value of parameter A1.T of menu
0VT, the set-up range is [0 ... 999] sec.
By adding +64 to the value of parameter A1.T of menu
0VT, the set-up range is [0 ... 999] min.
By adding +32 to the value of parameter A2.T of menu
0VT, the set-up range is [0 ... 999] sec.
By adding +64 to the value of parameter A2.T of menu
0VT, the set-up range is [0 ... 999] min.
By adding +32 to the value of parameter A3.T of menu
0VT, the set-up range is [0 ... 999] sec.
By adding +64 to the value of parameter A2.T of menu
0VT, the set-up range is [0 ... 999] min.
The value must be greater than the cycle time of the
output to which the HB alarm is associated
If set on "0", the LBA alarm is disabled.
If the LBA alarm is active, it can be cancelled by pres-
sing keys
+
value of the control output (OutP) or by switching to
Manual mode
If the LBA alarm is active, it can be cancelled by pres-
sing keys
+
value of the control output (OutP) or by switching to
Manual mode.
Unit of measurement digit / sec : by adding + 2 to
the value of the SP.R parameter in the INP menu
62
when the display indicates the
when the display indicates the