Configuration
This menu is used to configurare the control parameters in the Easy mode.
G
F
G
PV
---
SV
Enabling self-tuning, autotuning,
S. v
t
PV
softstart (**)
0
SV
Proportional band for heating
h. P b
or hysteresis for ON/OFF control
PV
1. 0
[0 ... 999.9] % f.s.
SV
Integral time for heating
h. I t
PV
[0.00 ... 99.99] min.
4. 0 0
SV
h. d t
Derivative time for heating
PV
[0.00 ... 99.99] min.
1. 0 0
SV
h. P . K
MAX power limit for heating
PV
100. 0
[0.0 ... 100.0] %
SV
KY. i
Hysteresis for Alarm 1
PV
- 1
[±999] scale points
SV
Adding +32 to the value of A 1.T in the 0VT menu,
the setting range is [0 ... 999] sec.
Adding +64 to the value of A 1.T in the 0VT menu,
the setting range is [0 ... 999] min.
Fourth menu to set up
S.tun
Continuous
autotunig
0
NO
1
YES
2
NO
3
YES
4
NO
5
YES
6
-
7
-
S.tun
Single action
Autotuning
8*
WAIT
9
GO
10*
WAIT
11
GO
12*
WAIT
13
GO
*) By adding the following figures to the value indicated in the
table it is possible to enable a series of supplementary functions:
+16 with automatic switch to GO if PV-SP > 0.5%
+32 with automatic switch to GO if PV-SP > 1%
+64 with automatic switch to GO if PV-SP > 2%
+128 with automatic switch to GO if PV-SP > 4%
**) For more information on the Self Tuning, Auto
Tuning, Soft Start functions, refer to the
Operational Notes paragraph.
Please note.:
If HEAT/COOL double action control type is ena-
bled (parameter [TR in menù KRD) then the COOL
action parameters cPb , cIt, cdt, cPK are displa-
yed, with the same ranges as the equipment
HEAT action parameters.
56
-Easy-
Selftuning
Softstart
NO
NO
NO
NO
YES
NO
YES
NO
NO
YES
NO
YES
-
-
-
-
Selftuning
Softstart
NO
NO
NO
NO
YES
NO
YES
NO
NO
YES
NO
YES