I I n n P P Input settings
This menu makes it possible to configure the parameters for the Controller input signals.
I
n
P.
PV
---
SV
Def. remote setpoint
S
P.
r
PV
[0 ... 1]
0
SV
tYP
Probe type, signal, enable custom linearization, and main input scale
PV
0
SV
T T Y Y P P
Probe type
Probe:
0
TC J °C
1
TC J °F
2
TC K °C
3
TC K °F
4
TC R °C
5
TC R °F
6
TC S °C
7
TC S °F
8
TC T °C
9
TC T °F
28
TC
29
TC
30
PT100 °C
31
PT100 °F
32
JPT100 °C
33
JPT100 °F
34
PTC °C
35
PTC °F
36
NTC °C
37
NTC °F
38
0...60 mV
39
0...60 mV
40
12...60 mV
41
12...60 mV
CUSTOM linearization:
Maximum Non Linearity Error for Thermocouples (TC), Thermoresistances (Pt100) and Thermistors (PTC, NTC). The error is
calculated as a departure from the theoretic value, referring in % terms to the of full scale value, expressed in degrees Celsius (°C)
Probe type
Probe
Thermocouples
TC J, K type
TC S, R type
TC T type
Using a Custom Linearization:
TC E, N, L type
TC B type
TC U type
TC G type
TC D type
TC C type
Thermistors
NTC
JPT100 / PTC
Thermoresistances Pt100
Digital filter on input
F
L
t
PV
[0.0 ... 20.0] sec
0. 1
SV
F
L
d
Digital filter on input display
PV
0. 5
[0 ... 9.9] scale points
SV
third menu to set up
Without dec. point
With dec. point
TC
0/1000
0.0/999.9
32/1832
32.0/999.9
0/1300
0.0/999.9
32/2372
32.0/999.9
0/1750
0.0/999.9
32/3182
32.0/999.9
0/1750
0.0/999.9
32/3182
32.0/999.9
-200/400
-199.9/400.0
-328/752
-199.9/752.0
CUSTOM
CUSTOM
CUSTOM
CUSTOM
-200/850
-199.9/850.0
-328/1562
-199.9/999.9
-200/600
-199.9/600.0
-328/1112
-199.9/999.9
-55/120
-55.0/120.0
-67/248
-67.0/248.0
-10/70
-10.0/70.0
14/158
14.0/158.0
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
the L0 message occurs when the variable assumes values less than the LO.S parameter or the
minimum calibration value. The KI message occurs when the variable assumes values greater than
the K'.S parameter of the maximum calibration value
Error
< 0,2 % f.s.
with range 0..1750 °C: < 0,2 % f.s. (t > 300 °C); for other ranges: < 0,5 % f.s.
< 0,2 % f.s. (t > -150 °C)
< 0,2 % f.s.; E type range 100..750 °C; N type range 0..1300 °C; L type range 0..600 °C
with range 44..1800 °C: < 0,5 % f.s. (t > 300 °C)
with range -200..400 °C: < 0,2 % f.s. (t > -100 C°)
< 0,2 % f.s. (t > 300 °C)
< 0,2 % f.s. (t > 200 °C
with range 0..2300 °C: < 0,2 % f.s.
< 0,5 % f.s.
< 0,2 % f.s.
with range -200..850 °C: precision better than 0.2 % f.s.
S S P P . . R R
Type of remote setpoint, Absolute / Relative
0
Digital (from serial line) Absolute
1
Digital (from serial line) Relative to SP or SP1 or SP2 sets
By adding +2 to the value set out in the table, the Set Gradient
(the G.SP parameter of the menu [FG) is expressed in digit/sec.
T T Y Y P P
Probe type
Probe:
42
0...20 mA
43
0...20 mA
44
4...20 mA
45
4...20 mA
46
0...10 V
47
0...10 V
48
2...10 V
49
2...10 V
50
0...5 V
51
0...5 V
52
1...5 V
53
1...5 V
54
0...1 V
55
0...1 V
56
200 mV...1 V
57
200 mV...1 V
58
Pers.. 10V-20mA -1999/9999
59
Pers. 10V-20mA
60
Pers. 60 mV
61
Pers. 60 mV
62
PT100 – JPT
63
PTC
64
NTC
If set to "0", the medium filter on the sample value is
excluded
64
Without dec. point
With dec. point
TC
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
-199.9/999.9
Linear custom
Linear custom
-1999/9999
-199.9/999.9
Linear custom
Linear custom
CUSTOM
CUSTOM
CUSTOM
CUSTOM
CUSTOM
CUSTOM