Lenze 8200 vector Montageanleitung Seite 193

15 ... 90 kw
Vorschau ausblenden Andere Handbücher für 8200 vector:
Inhaltsverzeichnis

Werbung

Code
Possible settings
No.
Name
Lenze
C0010
Minimum
0.00
output
uSEr
frequency
C0011
Maximum
50.00 7.50
output
uSEr
frequency
C0012
Acceleration
5.00
time main
uSEr
setpoint
C0013
Deceleration
5.00
time main
uSEr
setpoint
C0014
Operating mode
v
C0015
V/f rated
50.00 7.50
frequency
uSEr
à
C0016
V
boost
min
uSEr
EDK82EV903 DE/EN/FR 4.0
Important codes for quick commissioning
Selection
0.00
{0.02 Hz}
à
14.5 Hz
{0.02 Hz}
à
87 Hz
0.00
{0.02 s}
0.00
{0.02 s}
2
2
V/f characteristic control V ~ f
(linear characteristic with constant V
boost)
3
V/f characteristic control V ~ f
(square−law characteristic with constant
V
boost)
min
4
Vector control
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
{0.02 Hz}
0.00
{0.01 %}
l
Commissioning
IMPORTANT
l
C0010 not effective in the case of
650.00
bipolar setpoint selection (−10 V ...
+ 10 V)
l
C0010 only limits the analog input
1
l
In the case of a max. output
frequency > 50 Hz the switching
threshold of the auto DCB in C0019
has to be increased.
650.00
l
From software 3.5: If
C0010 > C0011, the drive does not
start when controller enable is set.
à
Speed setting range 1 : 6 for Lenze
geared motors: For operation with
Lenze geared motors has to be set
necessarily.
1300.00 Reference: frequency change 0 Hz ...
C0011
Additional setpoint ðC0220
l
l
Acceleration times that can be
activated via digital signals ð
C0101
1300.00 Reference: frequency change C0011...
0 Hz
Additional setpoint ðC0221
l
l
Deceleration times that can be
activated via digital signals ð
C0103
l
Commissioning is possible without
identifying motor parameters
min
l
Advantage of identification with
C0148:
– Improved smooth running at low
speeds
2
– V/f rated frequency (C0015) and
slip (C0021) are calculated and
saved. They do not have to be
entered
In the case of the first selection enter
the motor data and identify them
with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be set =
0 (automatic DC injection brake is
deactivated)
l
960.00
C0015 is calculated and saved
during the motor parameter
identification with C0148.
l
The setting applies to all permitted
mains voltages
à
40.00
device−dependent
Setting applies to all permitted mains
voltages
7
193