Commissioning

Parameter setting with the XT EMZ9371BC keypad

V/f characteristic control

7.4
Parameter setting with the XT EMZ9371BC keypad
,
Read the documentation for the keypad before starting work!
)
Note!
In the "Diagnostic" menu you can monitor the most important drive
parameters
7.4.1
V/f characteristic control
The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.
Switch−on sequence
1.
Plug in the keypad
2.
Ensure that controller inhibit is active after mains
connection
3.
Switch on the mains
4.
After approx. 3 s the keypad is in the operating level
and displays the output frequency (C0050) and the
device utilisation (C0056)
5.
For quick commissioning you select the "Quick
start" menu
Change the menu level with V
A
B
Change to the "Quick start" menu and from there to
the submenu "V/f quick" with z z Z z
Change to the code level with Z to parameterise
C
your drive
6.
Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
7.
If required, adapt the fixed setpoints JOG.
A
JOG 1 (C0037)
Lenze setting: 20 Hz
B
JOG 2 (C0038)
Lenze setting: 30 Hz
C
JOG 3 (C0039)
Lenze setting: 40 Hz
184
}
X3
20
28
misc001
ON
misc002
d
c
b
B
A
0050
00
0.00 Hz
0 %
9371BC004
d
c
b
B
A
p
SHPRG
Menu
4
2
Code
Para
Quick start
V / f q u i c k
9371BC007
z
d
c
b
B
A
Y Z
p
Menu
SHPRG
0034
00
Code
Para
y
0
A I N 1 r a n g e
9371BC008
l
Comment
Terminal X3/28 = LOW
The submenu "V/f quick" contains the
codes which you require for
commissioning a standard application.
The digital inputs are configured in the
Lenze setting:
X3/E1, X3/E2: activation of fixed
setpoints (JOG)
X3/E3: activation of DC injection brake
(DCB)
X3/E4: CW rotation/CCW rotation
Set the DIP switch on the standard I/O
to the same range (see Mounting
Instructions for the standard I/O)
Activation:
X3/E1 = HIGH, X3/E2 = LOW
Activation:
X3/E1 = LOW, X3/E2 = HIGH
Activation:
X3/E1 = HIGH, X3/E2 = HIGH
EDK82EV903 DE/EN/FR 4.0