Fuses And Cable Cross−Sections According To En 60204−1 - Lenze 8200 vector Montageanleitung

15 ... 90 kw
Vorschau ausblenden Andere Handbücher für 8200 vector:
Inhaltsverzeichnis

Werbung

5.3.2
Fuses and cable cross−sections according to EN 60204−1
Supply conditions
Range
Fuses
Cables
RCCB
Observe all national and regional regulations!
Operation at rated power
8200 vector
Type
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV153K4B
E82xV223K4B
E82xV303K4B
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV153K4B
E82xV223K4B
E82xV303K4B
1)
Earth−leakage circuit breaker
Operation with increased rated power
8200 vector
Type
Mains 3/PE AC 400 V − operation without mains choke/mains filter
E82xV153K4B
E82xV223K4B
E82xV303K4B
Mains 3/PE AC 400 V − operation with mains choke/mains filter
E82xV153K4B
E82xV223K4B
E82xV303K4B
1)
Earth−leakage circuit breaker
EDK82EV903 DE/EN/FR 4.0
Standard devices in the power range 15 ... 30 kW
Fuses and cable cross−sections according to EN 60204−1
Description
l
Utilisation category: only gG/gL or gRL
Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).
l
Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a
1−phase system
Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.
l
Earth−leakage circuit breakers must only be installed between mains supply and controller.
Rated fuse current
Fuse
Circuit−breaker
[A]
63
Operation only permitted with mains choke or mains filter
40
63
80
Rated fuse current
Fuse
Circuit−breaker
[A]
Operation only permitted with mains choke or mains filter
50
63
80
l
Electrical installation
Cable cross−section
Laying system L1, L2, L3, PE
B2
2
[A]
[mm
]
16
10
25
Cable cross−section
Laying system L1, L2, L3, PE
B2
2
[A]
[mm
]
16
25
5
1)
FI
C
2
[mm
]
[mA]
³ 300
16
10
³ 300
16
25
1)
FI
C
2
[mm
]
[mA]
10
³ 300
16
25
151