Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze 8200 vector Montageanleitung Seite 187

15 ... 90 kw
Vorschau ausblenden Andere Handbücher für 8200 vector:
Inhaltsverzeichnis

Werbung

Switch−on sequence
12.
Activate the operating mode "vector control"
(C0014 = 4)
Lenze setting: Linear V/f characteristic control
(C0014 = 2)
13.
Enter the motor data
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: depending on the controller
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: depending on the controller
E
Motor cosj (C0091)
Lenze setting: depending on the controller
14.
Start the motor parameter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller
If segment c becomes active again after approx.
D
30 s, inhibit controller again.
15.
Activate the motor temperature monitoring (C0119)
if you have connected a PTC or thermal contact to
terminal X2.2
Lenze setting: switched off
When all settings are complete:
16.
Select setpoint
17.
Enable the controller
18.
The drive is now running.
EDK82EV903 DE/EN/FR 4.0
Parameter setting with the XT EMZ9371BC keypad
d
c
b
B
p
SHPRG
Menu
0014
Code
Para
V e c t o r - C t r l
}
X3
20
Press TV
X3
20
28
}
X3
20
E.g. via potentiometer at
terminals 7, 8, 9
X3
20
28
l
Commissioning
Vector control
Comment
A
00
4
9371BC008
See motor nameplate
Enter the value for the motor circuit
configuration (star/delta) selected!
Enter the value for the motor circuit
configuration (star/delta) selected!
Only when the motor is cold!
Terminal X3/28 = LOW
28
misc001
l
Terminal X3/28 = HIGH
misc002
l
The identification starts:
– Segment c is off
– The motor consumes current and
makes a high−pitched" tone.
– The motor does not rotate!
l
Terminal X3/28 = LOW
28
l
Identification is completed.
misc001
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) =
Total resistance of motor cable
and motor
(¶ 194)
Possible settings
Terminal X3/28 = HIGH
misc002
If the drive does not start, additionally
press u
7
187

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis