Parameter setting with E82ZBC keypad

,
Read the documentation for the keypad before starting work!
After every mains switching, or after connection of the keypad during operation, the 10
codes that have been defined in code C0517 are immediately available.
By default, the user menu contains all codes required for commissioning a standard
application with linear V/f characteristic control:
Code
Designation
C0050
Output frequency
C0034
Range of setpoint selection
C0007
Fixed configuration digital
inputs
C0010
Minimum output frequency
C0011
Maximum output frequency
C0012
Acceleration time main
setpoint
C0013
Deceleration time main
setpoint
C0015
V/f rated frequency
C0016
V
min
C0002
Parameter set management
)
Note!
Via C0002 "Parameter set transfer/establishing the delivery status", you can
transfer configurations from drive controller to drive controller by means of
the keypad, or re−establish the delivery status by loading the Lenze setting
(e. g. if you've lost track during parameterising).
EDK82EV903 DE/EN/FR 4.0
Lenze setting
0
0
0.00 Hz
50.00 Hz
5.00 s
5.00 s
50.00 Hz
boost
device−dependent
l
Commissioning
Parameter setting with E82ZBC keypad
Display: output frequency without slip compensation
Standard I/O
X3/8: 0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
X3/1U: 0 ... 5 V / 0 ... 10 V
Application I/O
X3/2U: 0 ... 5 V / 0 ... 10 V
E4
E3
CW/CCW
DCB
Clockwise
DC injection
rotation/counte
brake
r−clockwise
rotation
Re−establish delivery status; transfer parameter sets by
means of the keypad; save, load, or copy own basic settings
7
E2
E1
JOG2/3
JOG1/3
Selection fixed setpoints
179