Electrical installation

Connection of relay output K1 and K2

5.6
Connection of relay output K1 and K2
Relay K1
Function
X1.2/K11
Relay output
normally−closed
contact
X1.2/K12
Relay mid−position
contact
X1.2/K14
Relay output
normally−open
contact
PES
HF shield termination by PE connection through shield clamp
)
Note!
ƒ
ƒ
ƒ
ƒ
ƒ
162
Relay position
switched
opened
closed
Switching of control signals:
– Use shielded cables
– HF shield termination by PE connection
– The minimum load for switching the signals through correctly is 12 V and
5 mA. Both values have to be exceeded at the same time.
Switching of mains potentials:
– Unshielded cables are sufficient
For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
The message that is output can be changed in code C0008 or C0415/1.
l
K11
K1
K12
K14
K21
K22
K2
K24
nc
Message
(Lenze setting)
TRIP
TRIP
X1.2
K11
K12
K14
X1.3
K21
K22
K24
nc
8200vec261
Technical data
250 VAC/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
EDK82EV903 DE/EN/FR 4.0