Models.
Available power ratings (VA / W).
Protection rating.
Dimensions (mm) Depth x Width x Height.
Weight (kg).
Safety.
Electromagnetic compatibility (EMC).
Marking.
Quality and environmental management.
Tab. 14. ADVANCE R2 general technical specifications.
Models.
Available power ratings (VA / W).
Technology.
Input.
Input type.
Number of cables.
Rated voltage.
Input voltage range.
Input frequency range.
Cold start (from batteries).
Inverter.
Waveform.
Power factor.
Rated voltage.
Output voltage accuracy (battery mode).
Total harmonic distortion (THDv), with linear load.
Frequency.
Transfer time, line mode to battery mode (normal mode).
Compatibility with APFC loads.
Performance at full load, in normal mode with battery 100%
charged.
Performance at full load, in battery mode.
Overload in line mode
Overload in battery mode.
Batteries (AGM sealed 3 - 5 years life). Only devices other than B1
Element voltage.
Capacity.
Number of batteries in device connected in series / group
voltage.
Number of accumulators in battery module connected in
series x no. packs in parallel / group voltage.
Low battery voltage.
Blocking voltage for group end of backup.
Internal battery charger.
Group floating voltage.
Maximum charge current.
Recharge time.
Other functions.
Cold start.
Emergency power off (EPO).
General.
IEC input connectors.
IEC output connectors.
Communication ports.
Connector for external EPO installation
Slot for optional cards.
Monitoring software.
USER MANUAL
ADVANCE R2
750VA / 450W
216x433x44 (1 U)
8.6
EN IEC 60240-1
EN IEC 60240-2
ISO 9001 and ISO 140001 (certified by SGS)
850VA / 595W
1000VA / 700W
Line-interactive with sine-wave output.
3 cables - Phase R (L) + Neutral (N) and earth.
220 / 230 / 240 V AC, selectable
With mains absent -backup mode- 50 / 60 ±1% Hz.
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
> 110 % ±10 % Audible alarm and fault after 1 min
> 120 % ±10 % Immediate fault
7 Ah
7.2 Ah
2 / 24 V DC
2 x 2/24 V DC
23 V
20.5 V
27.5 V
1 A (Devices other than B1) / 10 A (B1 devices)
IEC 60320 C14 10A
IEC 60320 C13
(1 x RS232 -DB9- and 1 x USB, functionally mutually exclusive).
1000VA / 600W
IP20
485x433x44 (1 U)
14.2
CE
ADVANCE T
1500VA / 1050W
2000VA / 1400W
Single-phase.
220 / 230 / 240 V AC
165..290 V AC
50 / 60 Hz (auto-detectable).
Yes
Pure sine wave.
0.7
±10%
< 5 % linear load
<10 % non-linear load
50 / 60 Hz.
4 ms
Yes
> 98 %
> 80 %
12 V DC
9 Ah
9 Ah
2 / 24 V DC
2 x 2/24 V DC
23 V
20.5 V
27.5 V
4 hours to 90%
Yes
Yes
Yes
SNMP
PowerMaster (free download).
SPS ADVANCE R2 & T UNINTERRUPTIBLE POWER SUPPLY (UPS)
1500VA / 900W
16.2
3000VA / 2100W
9 Ah
4 / 48 V DC
3 x 4/48 V DC
45 V
40 V
54.8 V
IEC 60320 C20
IEC 60320 C3 +
Terminals
55
Inhaltsverzeichnis
loading

Inhaltsverzeichnis