5.10 Change menu code
CHANGE MENU CODE
select
5.11 Change language
CHANGE LANGUAGE
select
Language options: NL, EN, DE, FR, PL, RO.
5.12 Calibration temperature
If the external room sensor is installed in an unfavourable position, the actual temperature and the
temperature measured by the PinTherm Infra Connect may differ. This temperature difference
can be compensated by setting a correction factor in this temperature calibration function.
For example:
The measured temperature is 18°C, but the PinTherm Infra Connect display
indicates 20°C. The difference in this example is 2°C too high. The
correction value must be set to -2°C.
CALIB. TEMP.
select
SELECT NEW CODE
1000
OK
changes the
flashing digit
to go one digit up
New menu code
SELECT LANGUAGE
ENGLISH
OK
select the desired
language
CALIB. TEMP.
+ 0.0°C
OK
changes the
flashing digit
to go one digit up
Correctionvalue is adjustable
from -3,5°C to +3,5°C
EN
OK
back to the
menu
OK
back to the
menu
OK
back to the
menu
11