45.1 modbus-tcp

Configure Modbus TCP/IP server settings.

45.1.1 modbus-tcp operation

Enable or disable the Modbus TCP/IP server.
Mode: Global Config Mode
Privilege Level: Operator
Format: modbus-tcp operation
no modbus-tcp operation
Disable the option
Mode: Global Config Mode
Privilege Level: Operator
Format: no modbus-tcp operation

45.1.2 modbus-tcp write-access

Enable or disable the write-access on Modbus TCP/IP registers. - Possible
security risk, as Modbus TCP/IP communication is not authenticated - .
Mode: Global Config Mode
Privilege Level: Operator
Format: modbus-tcp write-access