Herunterladen Diese Seite drucken

CGS XT-T1 Betriebsanleitung Seite 150

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Resistance transmitter and resistor/potentiometer
Designation
Resistance transmitter
E
Resistance/potentiometer
1
The accuracy is related to the maximum measurement range. The linearization accuracy decreases at lower measurement ranges.
Ambient temperature influence
Connection type
Resistance transmitter
Resistance/potentiometer
Sensor line resistance
Sampling rate
Input filter
Voltage, current (standard signals)
Designation
Voltage
Current
Ambient temperature influence
Deviation below/above the mea suring
range
Sampling rate
Input filter
The accuracy is related to the maximum measurement range. The linearization accuracy decreases at lower measurement ranges.
1
Measuring circuit monitoring
The device behavior in the event of a fault is configurable.
Measuring probe
RTD
temperature
probe
Resistance/po-
tentiometer
Resistance
trans-
mitter
Thermocouple
Current 0 to 20 mA
Current 4 to 20 mA
Voltage 0 to 10 V
Measuring range
0 to 4000 W
0 to 400 W
0 to 4000 W
£ 100 ppm/K
Three-wire circuit
Two-wire/three-wire circuit
Max. 30 W per line
150 ms
Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s
Measuring range
0 to 10 V
2 to 10 V
4 to 20 mA
0 to 20 mA
£ 100 ppm/K
According to NAMUR recommendation NE 43 (only current input 4 to 20 mA)
150 ms
Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s
Measuring range
Measuring range
underflow
overflow
++
++
---
++
---
---
++
++
---
++
++
++
---
++
Product:
Temperature controller XT-T1
Accuracy
1
£ 0.1 %
£ 0.1 %
£ 0.1 %
Accuracy
1
£ 0.1 %
£ 0.1 %
£ 0.1 %
£ 0.1 %
Short-circuit
Break (probe/line) Polarity
(probe/line)
++
++
---
++
(+)
(+)
a
b
---
++
---
---
++
++
---
---
Revision 2.0 – Issue September 2018
Measuring current
50 mA
500 mA
50 mA
Input resistance or bur den
voltage
> 500 kW
> 500 kW
< 2.5 V
< 2.5 V
---
---
---
(+)
c
---
++
++
150/166