Parameter
Scaling start
E
Scaling end
Decimal places
Measured value offset
Filter time constant
?
KTY at 25 °C
(setup only)
Cold junction tempera ture
(setup only)
Constant
(setup only)
Fine adjustment
(device only)
?
Actual start value
Actual end value
Target start value
Target end value
Additional functions
(setup only)
Selection/text/value
-1999 to 9999 (0)
-1999 to 9999 (100)
Auto
XXXX.
XXX.X
XX.XX
X.XXX
-1999 to 9999 (0)
0 to 100 (0.6)
0 to 4000 (2000)
Internal
Constant
0 to 100 (25)
Off
On
-1999 to 9999 (0)
-1999 to 9999 (100)
-1999 to 9999 (0)
-1999 to 9999 (100)
Expansion 1 to
expansion 5
Product:
Temperature controller XT-T1
Description
Lower limit of measuring range or display range (depen-
ding on sensor and linearization)
Upper limit of measuring range or display range (depen-
ding on sensor and linearization)
Number of pre-decimal and decimal places for the nume-
rical display of the measured value
Automatic
No decimal place
One decimal place
Two decimal places
Three decimal places
Correction value for the measured value
All measured values are moved by the same cor rection
value (see fine adjustment).
Time constant (in seconds) for adjusting the digital input
filter (0 s = filter off)
For 2-L RTD temperature probe with linearization KTY11-6
2-L: resistance (in Ω) at 25 °C / 77 °F
Only with thermocouple: selection of the cold junc tion
temperature
Internal temperature is used.
Constant temperature can be entered.
Constant cold junction temperature
The function for performing fine adjustment is not active.
This function is available in the setup program un der
„Online parameter".
The function is active.
Fine adjustment: device measured value at the lower
measuring point
In contrast to measured value offsetting, which is used to
specify a constant correction value for the entire charac-
teristic line, fine adjustment can also be used to change
the gradient of the characteris tic line.
Fine adjustment: device measured value at the up per
measuring point
Fine adjustment: reference value at the lower mea suring
point
Fine adjustment: reference value at the upper measuring
point
Reserved functions for service purposes. Only ac tivate
when instructed to do so by service person nel!
Click checkbox to activate the function.