Parameter
Behavior after power on
(setup only)
E
Time display
Timer time
Lead time
After-run time
Acknowledgement sig nal
Start signal
Abort signal
Stop signal
Selection/text/value
Abort
Continuation
Restart
mm:ss
hh:mm
dd:hh
00:00 to 59:59
00:00 to 23:59
00:00 to 99:23
0 to 9999
-1 to 9999 (0)
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Product:
Temperature controller XT-T1
Description
Timer aborted
Timer continues to run for the remaining running time.
Any minute of remaining running time that is not com-
pleted is repeated; examples (mm:ss):
power off at 09:01, continuation at 10:00
power off at 09:00, continuation at 09:00
Timer restarts at the timer time.
The lead time is not considered in case of a restart.
Timer time unit (for input and display on the device)
Minutes:Seconds
Hours:Minutes
Days:Hours
Time after timer start
The setting range depends on the configured time unit:
mm:ss
hh:mm
dd:hh
Time before timer start (in seconds)
Time after timer end (in seconds)
-1 = active until acknowledged
The end signal is active during the after-run time.
Only if after-run time ≠ 0: signal (active for rising edge)
to acknowledge the end signal
Signal (active for rising edge) to start the timer
The start signal only works while the timer is not running
or during the after-run time (not during the lead time or
runtime).
Signal (active for rising edge) to abort the timer
The abort signal only works during the runtime (not
during the lead time or after-run time).
Signal (high active) for stopping the timer
The stop signal only works during the lead time and
runtime (not during the after-run time).