Behaviour after power on
The controller outputs are inactive during the initialization phase (output level 0 %, relay in standby mode).
E
9.9.2 Controller input
The controller input signals are assigned in this menu.
Parameter
Controller actual value
Controller setpoint value
Signal 1 setpoint changeo-
ver
Signal 2 setpoint changeo-
ver
Manual/auto change over
signal
Manual mode signal in-
hibition
Parameter block changeo-
ver signal
Controller signal on
Controller signal off
9.9.3 Autotuning
This menu is used to implement settings for the autotuning.
Parameter
Method
?
Inhibit
(setup only)
Controller output type 1
Selection/text/value
Analog selector
Analog input
Analog selector
Current setpoint value
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Digital selector
No selection
Selection/text/value
Step response
Oscillation
Enabled
Inhibited
Automatic
Relay
Analog
Solid state/logic
Product:
Temperature controller XT-T1
Description
Analog signal as actual value of the controller
Analog signal as controller setpoint value
Signal (bit 0) for controlling setpoint changeover
Signal (bit 1) for controlling setpoint changeover
Signal (high-active) for changeover to manual mode
Signal (high active) for inhibiting manual mode
Signal (high-active) for changeover from parame ter block
1 to parameter block 2
Signal (high-active) for switching on the controller
Signal (high-active) for switching off the controller
Description
Step response method
Oscillation method
Autotuning is enabled.
Autotuning is inhibited.
Type of the first controller output
The cycle time is calculated on the basis of the type of
controller output.
Automatic setting based on the configuration
If the controller output signal is assigned to several
digital outputs (e.g., output 1: relay; output 4: log ic), the
digital output with the smaller number is rel evant (here:
output 1).
Relay output
Analog output
PhotoMOS® relay output or logic output