9.9.6 Setpoint values
One of four (switchable) setpoint values is used a a controller setpoint value. For each of these setpoints, certain spe-
cifications can be made here that are of importance, for example, when entering the setpoint value. The setpoint itself
can also be set here.
Parameter
Min. limit
Max. limit
Setpoint value
9.9.7 Ramp function
The ramp function is used for a constant change of setpoint value w, starting from the current ramp value (= actual value
at time t
of the setpoint value change) up to the ramp end value SP (default setpoint value).
0
A tolerance band can be set around the setpoint value curve to monitor the actual value. If the actual value deviates
from the tolerance band, the tolerance band signal is activated.
NOTE!
If the device operates as a program controller, the ramp function is not active.
NOTE!
The ramp function is not active in manual mode. After switching from manual mode to automatic mode, the actual
value is applied as the current ramp value (ramp starts).
Parameter
Function
Pos. gradient
Neg. gradient
Tolerance band
Product:
Temperature controller XT-T1
Selection/text/value
-1999 to 9999 (0)
-1999 to 9999 (400)
-1999 to 9999 (0)
Selection/text/value
Off
Per minute
Per hour
Per day
0 to 999
0 to 999
0 to 9999
Revision 2.0 – Issue September 2018
Description
Minimum admissible setpoint value (lower input limit)
Maximum admissible setpoint value (upper input limit)
Fixed setpoint value (input limits dependent on min. limit
and max. limit)
Description
Ramp function is not active.
Ramp function is active.
Unit of ramp slope: Kelvin per minute
Kelvin per hour
Kelvin per day
Value for positive ramp slope
Value for negative ramp slope
Amount of admissible upward and downward devi ation of
the actual value (standard tolerance band around setpoint
value)
E
131/166