Parameter
Temp. unit interface
E
9.4 Display / Operation
Settings are implemented in this menu that affect the function of the displays and the device buttons.
Parameter
Display 1
Display 2
Display 3
Display 4
Timer start display change
Auto save
(setup only)
Setpoint value adjust ment
(setup only)
Level inhibit
(setup only)
?
Time-out operation
Contrast
Selection/text/value
°C
°F
Selection/text/value
Analog selector
Analog input
Analog selector
Current setpoint value
Analog selector
No selection
Analog selector
No selection
Without function
Timer remaining run ning
time
Timer runtime
Yes
No
Yes
No
None
Conf
Conf + para
Conf + para + prog
Complete
30 to 180
0 = Switched off
1 to 10 (8)
Product:
Temperature controller XT-T1
Description
Temperature unit for temperature values trans ferred via
the serial interface.
Description
Analog signal that is shown in the first 18-segment dis-
play (top, white).
Analog signal that is shown in the second 18-seg ment
display (bottom, green).
Analog signal that is shown in the top line of the pixel
matrix display (only for formats 108H, 108Q, and 104).
Analog signal that is shown in the bottom line of the
pixel matrix display (only for formats 108H, 108Q, and
104).
Display change when starting the timer:
No display change
Display of the remaining running time
Display of the runtime
Editing mode is automatically exited after after a certain
period and a change is applied.
The „Menu/OK" button must be pressed to exit ed iting
mode with the application of a change.
The current setpoint value can be entered directly in the
basic status using the „Up" and „Down" but tons.
Setpoint value adjustment is not allowed in the ba sic
status.
Access to the individual levels can be inhibited:
No level inhibited
Configuration level inhibited
Configuration level and parameter level inhibited
Configuration level, parameter level, and program editor
level inhibited
Configuration level, parameter level, program edi tor
level, and user level inhibited
Time period (in seconds), after which the device automa-
tically returns to the basic status if no key is pressed.
Contrast of the displays
Revision 2.0 – Issue September 2018
112/166