Parameter
Response in case of a fault
Switch-on delay
(setup only)
Switch-off delay
(setup only)
Pulse time
(setup only)
Inhibit signal
(setup only)
Self-locking
(setup only)
Acknowledgement sig nal
(setup only)
Additional functions
(setup only)
Function
For the AF1 to AF6 alarm functions, the final limit value depends on the setpoint value – the entered limit value is
added to or subtracted from the setpoint value. The AF7 and AF8 alarm functions work with a fixed limit value which
corresponds to the limit value entered.
ð
chapter 9.12.1 „Alarm functions and switching behavior"
Startup alarm suppression
Function of the startup alarm suppression:
After power on, the alarm signals for the limit value monitoring function remains inactive, even if the actual value is
in the alarm range.
If the limit value or setpoint value is changed so that the actual value is then within the alarm range, while the actual
value is outside of the alarm range, the alarm signal remains inactive.
The limit value monitoring only starts to operate according to its alarm function again once the actual value has left
the alarm range. This means that the alarm signal remains inactive until the actual val ue returns to the alarm range.
Behaviour after power on
The output signal status is not saved via power off. Limit value monitoring starts after completion of ini tialization ac-
cording to its configuration.
Product:
Temperature controller XT-T1
Selection/text/value
Off
On
0 to 9999
0 to 9999
0 to 9999
Digital selector
No selection
Off
On
Always acknowledge able
Digital selector
No selection
Expansion 1 to
expansion 5
Revision 2.0 – Issue September 2018
Description
Output signal in the event of a fault (e.g., in the event of
overrange or underrange)
Output signal inactive
Output signal active
Delay time (in seconds) for activation of the output signal
if alarm condition is present.
Delay time (in seconds) for deactivation of the out put
signal if alarm condition is no longer present.
Output signal is deactivated automatically after this time
(in seconds).
Signal (high-active) for suppressing the output sig nal
Self-locking is not active.
The output signal is reset as soon as the actual value is
back in the valid range.
Self-locking is active.
Self-locking can only be acknowledged if the actu al value
is back in the valid range.
Self-locking is active.
Self-locking can always be acknowledged.
Signal (high-active) for acknowledging the output signal
in case of self-locking
Expansion 1 to 5: Reserved functions for service purpo-
ses. Only activate when instructed to do so by service
personnel!
Click checkbox to activate the function.