Configuring the Water Management Server
Configuring hygiene functions
Configuring regeneration time
Overview of configurable parameters:
Regeneration time Deactivation
Please note:
A regeneration time can be set between the flushes of the individual fittings
that are disinfected by the respective thermal disinfection. If necessary, a stor-
age tank can be heated up again during this time so as to ensure sufficiently
high water temperatures.
Configuring re-flushing
Overview of configurable parameters:
Re-flushing
Please note:
After the thermal disinfection has been completed, the fittings can be re-
flushed with cold water to avoid the danger of scalding.
If you want to use re-flushing, switch it on with "Configuration — Post Flush
— On/Off".
If you have switched on re-flushing, select a suitable flow time.
The re-flushing time starts 5 minutes after the end of the thermal disin-
fection.
Specifying a sequence
The subscribers are thermally disinfected one after the other.
If you want to thermally disinfect several fittings at the same time, these need
to be placed into a group. Remember this during group management (see
"2.4 Grouping fittings" on page 171).
The order in which the fittings/groups are flushed through during thermal dis-
infection can be chosen as required. Pay attention to pipeline routing when
specifying this sequence.
»
Use the arrow keys to sort the subscriber fittings or groups into an appro-
priate order.
178
Configurable selection
5 min to 30 min
Configurable selection Configurable selection Factory setting
On/Off
Flow time
5 s to 3 min
Factory setting
Deactivation
Off