Configuring the Water Management Server
Configuring hygiene functions
»
Configure the automation according to the specifications of your drinking
water installation. In doing so, observe the following information about
configuration parameters.
Schell Web-App
https://sws.schell.eu/schell/assets/schell-embedded-ui/01.14B10/app.html
© Copyright 2021 SCHELL GmbH & Co. KG
Configuring flow time
Overview of parameters:
Configurable selection
Flow time
0.5 min to 10 min
Mode configuration
Overview of configurable parameters:
Mode
Configurable selection
Cyclic
1 – 240 h
By time and week-
Time, weekday
day
(Mon–Sun)
Temperature
Temperature sensor
(max. every 12 h)
Overshoot/undershoot
Temperature
Start by signal
Input 1 to 4
Set the mode of the stagnation flush (cyclic or according to time and weekday
or temperature-controlled) according to your requirements.
Advice on "Temperature" mode
When triggered by a temperature sensor, the stagnation flush is carried out
once the selected temperature is reached. The configured flow time then runs
in full until expiry. After this, another flush process is triggered after 12 hours
at the earliest.
Fig. 20: Stagnation flush configuration, example: Setting flow time
Configurable selec-
tion
Connected tempera-
ture sensor
Overshot by
Undershot by
20 °C – 80 °C
Scroll 
Selection
Factory setting
Factory setting
Every 24 h
EN
Apply