Configuring the Water Management Server
Configuring hygiene functions
Warning!
Risk of scald injury from hot water.
During a thermal disinfection, hot water exits the respective fittings
for an extended period of time.
> The facility manager must make sure that nobody is within range
of the respective fittings or can gain access to this area while ther-
mal disinfection is being carried out.
Notice
>
Smoke alarms can be triggered by the formation of steam during
a thermal disinfection.
Configuring output signal and termination signals
See "Configuring output signal and termination signals" on pagePage 174.
Configuring a termination sensor
Overview of configurable parameters:
Configurable selection Configurable selection Factory setting
Termination sensor
On/Off
Termination crite-
Temperature
rion
Temperature sensor
Please note:
Thermal disinfection can be terminated by the Water Management Server if
proper disinfection of the drinking water installation is not guaranteed as a
result of the system temperatures.
Switch on the termination sensor under "Configuration — Abort Sensor —
Abort Sensor" if you wish to use the sensor.
If you have connected additional temperature sensors to the SWS bus ex-
tenders, select the appropriate sensor as the termination criterion. Set the
temperature that will terminate the thermal disinfection when it is exceeded.
The start and termination sensors must not be the same.
Off
25 °C to 80 °C
Connected temperature
sensor
EN
177