Linear heat detector ADW 511A Transafe
13

Appendices

Classification temperatures [in °C] of detectors, extract from EN 54.5:2000
Detector
Typical application temperature:
This is the temperature to which an installed detector can be exposed over an extended
period without the event of fire.
NOTE: This temperature lies 29°C below the static response temperature in accordance with
Maximum application temperature:
This is the maximum temperature to which an installed detector can be exposed, albeit only
briefly, without the event of fire.
NOTE: This temperature lies 4°C below the static response temperature in accordance with
Static response temperature:
Maximum temperature to which a detector can be briefly exposed without the event of fire.
NOTE: Temperature increase speeds of around 0.2 K min
Bosch Sicherheitssysteme GmbH
Typical applica-
class
tion tempera-
ture
A1
25
A2
25
B
40
C
55
D
70
E
85
F
100
G
115
the class stated on the detector and pursuant to the specifications in the
table.
the class stated on the detector and pursuant to the specifications in the
table.
measuring the static response temperature; however, lower speeds can be
required in special cases.
Maximum
Minimum static
application
response tempera-
temperature
50
50
65
80
95
110
125
140
Installation Guide
Appendices | en
Maximum static
response temperature
ture
54
65
54
70
69
85
84
100
99
115
114
130
129
145
144
160
-1
have been established as usual for