en | Trouble shooting
10

Trouble shooting

Do not interfere with the PC board.
Faulty PC boards must be replaced and returned to the manufacturer.
No LED display,
fire panel malfunc-
tioning
General fault
FAULT LED lights up
Leakage fault
FAULT LED
flashes 1:1
Pinching fault
FAULT LED
flashes 3:1
Wrong initial setup
fault
all LEDs
flashing 3:1
No LED display,
fire panel in alarm
status,
no fire
Differential alarm,
no fire
ALARM DIFF LED
activated
Maximum alarm, no
fire
ALARM MAX LED
activated
BDL -F.01U.004.036 | A2 | 2006.11
Display
Status
No power
Voltage available
Display
Check hoses in detector box
Check testing device
Check supply to sensor tube
All the above items OK
Check hoses in detector box
Check testing device
Check sensor tube for leak-
age
Perform visual check of
entire sensor tube system
Check program selection
switch setting
Check Reset input
Check alarm function via pro-
gram selection switch, posi-
tion A
Check fire panel
Check program selection
switch setting
Check alarm function via pro-
gram selection switch, posi-
tion A
Check program selection
switch setting
Check alarm function via pro-
gram selection switch, posi-
tion A
Installation Guide
Measure
Measure voltage
on terminal 1/2
Measure
Linear heat detector ADW 511A Transafe
Possible causes
Error in fire panel
Supply interrupted
Fuse in ADW faulty
PC board faulty
Possible causes
Internal hoses not fitted or
pinched
Motor wiring detached
Motor or gears faulty
Pressure pump faulty
Faulty connection to detector
box
Plastic hose leaking or pinched
Watchdog reset fault
PC board or software fault
Small leak in internal hose
Small leak in pressure pump
Small leak in sensor tube (hair-
line crack, loose screw joint)
Sensor tube pinched at detec-
tion point
Switch incorrectly set
Input under continuous activa-
tion
PC board in ADW faulty
PC board or software fault
Wiring error
Error in fire panel
Sensitivity level set incorrectly
for current application
PC board in ADW faulty
PC board or software fault
Sensitivity level set
incorrectly for current applica-
tion
PC board in ADW faulty
PC board or software fault