58
en | Technical data
12
Technical data
Operating voltage
Maximum current consumption
Maximum current consumption
Maximum permissible voltage drop
in the electrical installation
Maximum permissible contact load in alarm relay
RS232 serial interface
Test interval
Temperature range
Sensitivity range
Permissible relative humidity
Detector box
Sensor tube
Approvals
Tested pursuant to
BDL -F.01U.004.036 | A2 | 2006.11
–
in standby
–
for diff/max alarm
–
for pre-alarm and diff/max alarm
–
for faults
–
during testing
–
in standby
–
for diff/max alarm
–
for pre-alarm and diff/max alarm
–
for faults
–
during testing
–
for 12 V DC
–
for 24 V DC
–
Detector box
–
Sensor tube
–
Detector box
–
Sensor tube
–
Protection type
–
Material
–
Color
–
Dimensions (W x H x D)
–
Weight
–
Permissible length for tunnel application
(incl. ascent to ceiling)
–
Permissible length for other applications
(incl. ascent to ceiling)
–
Inner/outer diameter
Installation Guide
Linear heat detector ADW 511A Transafe
10.5 to 30 V DC
for 12 V DC (measured at 10.5 V DC)
approx. 114 mA
approx. 124 mA
approx. 135 mA
approx. 103 mA
approx. 127 mA
for 24 V DC (measured at 14 V DC)
approx. 90 mA
approx. 99 mA
approx. 108 mA
approx. 81 mA
approx. 102 mA
1.5 V DC
10 V DC
50 V DC / 1 A
9-pole D-SUB plug
8 hours (adjustable)
-20°C to +50°C
-40°C to +160°C
pursuant to EN 54-5, A1-G
95 %
100 %
IP 65
PE glass fiber reinforced
gray, RAL 7000
160 x 205 x 93 mm
1.7 kg
20 m to 130 m
20 m to 80 m
4 mm/5 mm
VdS, UL
EN 54 and 89/336/EWG (EMV)
Bosch Sicherheitssysteme GmbH