en | Installation
7.4

Electrical connection

The detector box is equipped as standard with an M20 cable screw connector. An additional
M20 cable screw connector can be fitted to a reserve drill hole (plugged) if required.
Electrical connections are established via pluggable screw terminals. The system is equipped
with individual terminal blocks for the power supply, relay contacts, reset input and open col-
lector outputs. The serial interface is connected via a D-SUB9 socket.
NOTICE!
i
The cables inside the detector box must be fed to the terminal blocks via the shortest possi-
ble route.
7.4.1

Terminal assignment

The "Fault" relay is activated in standby mode; i.e. the contact is closed between terminal 15/
13 and open between 15/14.
Terminal
BDL -F.01U.004.036 | A2 | 2006.11
1 2 3 4
5 6
7 8 9 10
1
+10.5 to +30 V DC
2
3
+10.5 to +30 V DC
4
5
+ External Reset
6
- External Reset
7
OC output alarm
8
OC output fault
9
OC output reserve
10
Alarm relay NO
11
Alarm relay NC
12
Alarm relay C
13
Fault relay NO
14
Fault relay NC
15
Fault relay C
16
Reserve relay NO
17
Reserve relay NC
18
Reserve relay C
10 11
11 12
12 13
13 14
14 15
Signal
0 V
0 V
Installation Guide
Linear heat detector ADW 511A Transafe
15 16
16 17
17 18
18
Address
DC IN
DC OUT
Reset
Open collector outputs
Relay contacts for alarm
Relay contact for fault
Additional relay contacts
Bosch Sicherheitssysteme GmbH