Linear heat detector ADW 511A Transafe
7.2

Sensor tube installation

Only one sensor tube can be connected to each detection box.
The sensor tube must be installed in accordance with the following guidelines:
Bosch Sicherheitssysteme GmbH
For installation in tunnels see planning notes on page 36.
The sensor tube should not be installed adjacent to, below or above strip lighting. If
this is unavoidable, make sure a minimum distance of 0.5 m is adhered to.
When installing the sensor tube, make sure the lateral viewing angle is not
obstructed. See image on left:
Right
2
1
3
1 m
1 m
Deviations from the above guidelines are permissible in order to circumvent obstruc-
tions in the ceiling construction (openings, beams etc.).
When installing in tunnels, make sure that the changes in direction necessary to cir-
cumvent obstacles are at angles of 45°.
Tube sections will require mechanical protection if directional changes are only pos-
sible at an angle of 90°.
The maximum permissible sensor tube lengths (incl. the value up to the ceiling)
specified on page 36 must be adhered to.
It can be installed to the underside of cable ducts as long as the distance to the ceil-
ing is not greater than 0.5 m.
At tunnel entrance portals, a distance of 25 m must be maintained between the sen-
sor tube end and the portal.
Secure the sensor tube with rust-proof screws only.
It is attached directly to the ceiling using plastic sliding brackets.
The sensor tube must be fixed in place using metal pipe clips when used in areas
with higher ambient temperatures.
The recommended distance between each clip is 0.8 m.
The sensor tube and pipe clips must be installed in a straight line to allow for longi-
tudinal pipe expansion due to fluctuations in temperature.
Do not undercut the minimum bending radius of 5 cm for the copper sensor tube or
the plastic hose.
Installation Guide
1
Cable duct
2
Sensor tube
3
Viewing angle
4
Viewing angle
obstructed
Installation | en
Wrong
2
1
4
1 m
1 m
BDL -F.01U.004.036 | A2 | 2006.11
41