Linear heat detector ADW 511A Transafe
3.4
Tunnel with curved roof or round construction and 2 to 3 traffic
lanes.
3.5
Parking halls, multi-story parking areas, vehicle decks on ships
and similar applications
4
Ordering information
Transafe ADW 511A signal analysis and monitoring module of
the linear maximum and differential heat detector
Copper pipe Ø 5 mm x 5.5 m
with 6 plastic clamps and 1 Serto screw joint
Plastic hose (polyamide)
DU = Delivery unit
Pc = Piece = 25 meters for hose
Bosch Sicherheitssysteme GmbH
–
Where possible, the sensor tube should be mounted in the center of the tunnel ceil-
ing
(max. permissible side tolerance ± 0.5 m).
–
The maximum permitted sensor tube length is 130 m.
SENSTUBE
–
Maximum permissible distance 1 between the sensor tubes is 7.0 m.
–
Maximum permissible distance 2 between sensor tube and tunnel wall is 3.5 m.
–
The maximum permitted sensor tube length is 130 m.
2
1
SENSTUBE 1
1
1
2
Designation
Installation Guide
Ordering information | en
SENSTUBE
SENSTUBE 2
DU
Pc
Pc
Pc
BDL -F.01U.004.036 | A2 | 2006.11
37
2
ADW 511A
2
Product ID
F.01U.523.579
4.998.102.378
F.01U.029.220