Linear heat detector ADW 511A Transafe
7.4.2

Power supply

The power supply to the ADW 511A must always have an emergency backup supply and is fed
from the fire panel to the devices via a stub or ring connection. Power supply can be local and
individual or local and in zones.
Stub power supply
Ring power supply
Power supply local, individual
ADW 511A
1 2 3 4
+
7.4.3

Reset input

The optocoupler input RESET EXTERN (terminal 5 and 6) can be
switched via plus or minus. The input will respond to a pulsed
signal. It works in a range from +10 to +30 VDC and in a pulse
bandwidth of 0.5 to 5 s.
The application of a continuous signal will deactivate the
ADW 511A. A "Wrong Initial Setup" fault will be reported
after approximately 20 seconds due to safety reasons.
1 Reset pulse, plus-switched, fire panel power supply
2 Reset pulse, minus-switched, fire panel power supply
3 Reset pulse, plus or minus switched, local supply
Bosch Sicherheitssysteme GmbH
ADW 511A
1 2 3 4
+
ADW 511A
1 2 3 4
+
+
ADW 511A
1 2 3 4
+
\=
\=
External reset
ADW 511A
1
2
3 4
ADW 511A
1 2 3 4
Power supply local, in zones
Installation Guide
Installation | en
ADW 511A
ADW 511A
1
2
3 4
1
ADW 511A
ADW 511A
1 2 3 4
1 2 3 4
ADW 511A
1 2 3 4
+
\=
+ −
1
2
3 4
+ −
+ −
+ −
1
2
3 4
+
− + −
+ −
1
2
3 4
+ −
+ −
BDL -F.01U.004.036 | A2 | 2006.11
47
2
3 4
ADW 511A
1 2 3 4
5
6
1
+
5
6
2
+
5
6
3
+

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis