Pump operation

11.1

Operating elements

Fig. 34: Operating button
ON
1 2
Fig. 35: DIP switch
128
The D component is set to zero at the factory because this setting is suitable for many ap-
plications.
Change the parameters in small steps only and monitor the effects on the system continu-
ously. Only a trained expert in the field of control engineering may carry out adjustment of
the parameter values.
Control component
Factory setting
P
0.5
0.5 s
I
D
0 s
(= deactivated)
Table 17: PID parameter
The sign for the P component determines the control's direction of control action.
Positive PID-Control (default):
If the P component is positive, the control system reacts to falling below the setpoint by in-
creasing the pump speed.
Negative PID-Control
If the P component is negative, the control system reacts to falling below the setpoint by re-
ducing the pump speed.
NOTICE
Possible malfunction in case of incorrect direction of control ac-
tion for PID control!
The pump runs only at minimum or maximum speed. It will not react to
changes in the parameter values.
• Check the controller's direction of control action.
Carry out settings by turning and pressing the operating button. Turn the operating button
to the left or right to browse the menus or configure settings.
Rotate
: Menu selection and parameter setting.
Press
: Activation of menus or confirming settings.
The DIP switch is beneath the housing cover.
No.
Function
1
Switching between default and service mode. For additional information, see
section "Activating/Deactivating service mode"
2
Activating or deactivating access disable. For additional information, see sec-
tion "Activating/Deactivating access disable"
Table 18: DIP switch
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA B • Ed.01/2023-05
Setting range
Incrementation
-30.0 ... 2.0
0.1
-1.99 ... 0.01
0.01
0.00 ... 1.99
0.01
2.0 ... 30.0
0.1
10 ms ... 990 ms
10 ms
1 s ... 300 s
1 s
0 ms ... 990 ms
10 ms
1 s ... 300 s
1 s