Wilo Stratos GIGA Einbau- Und Betriebsanleitung Seite 138

Vorschau ausblenden Andere Handbücher für Stratos GIGA:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

en
No.
Name
4.3.6.0
AUX
4.4.0.0
Device data
4.4.1.0
Pump name
4.4.2.0
Software version
of user controller
4.4.3.0
Software version
of motor con-
troller
5.0.0.0
Service
5.1.0.0
Multi pump
5.1.1.0
Operating mode
5.1.2.0
Setting, MA/SL
5.1.3.0
Pump cycling
5.1.3.1
Manual pump
cycling
5.1.3.2
Internal/external
5.1.3.3
Internal: Time in-
terval
5.1.4.0
Pump enabled/
disabled
5.1.5.0
5.1.6.0
SBM
5.1.7.0
External off
138
Type Symbol
Values/explanations
State of "AUX" terminal
Displays device data
Example:
Stratos GIGA 40/4-63/11 (display in ticker
format)
Displays the software version of the user
controller
Display the software version of the motor
controller
Service menus
Twin-head pump
Main/standby operation
±
Parallel operation
Manually switches from "Main pump" to
±
"Standby pump" (partner pump) mode
Carries out pump cycling independent of
±
the countdown
Internal pump cycling
±
External pump cycling
Can be set between 8 h and 36 h in 4 h
±
steps
Pump enabled
±
Pump disabled
Individual fault signal
±
Collective fault signal
Individual readiness signal
±
Individual run signal
Collective readiness signal
Collective run signal
Individual External off
±
Collective External off
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA B • Ed.01/2023-05
Display conditions
Only the basic pump model appears
on the display; version names are
not shown
Only displayed when DP is active
(incl. sub-menus)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump), see "AUX" terminal
Displayed when internal pump cyc-
ling is activated
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump) and for SBM function
standby/run
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)
Only displayed at the MA (main
pump)