No.
Name
5.7.0.0
Other settings 1
5.7.1.0
Display orienta-
tion
5.7.2.0
Delivery head
correction for in-
line pumps
5.7.2.0
Delivery head
correction for
monobloc pumps
5.7.5.0
Switching fre-
quency
5.7.6.0
SBM function
5.7.7.0
Factory setting
5.8.0.0
Other settings 2
5.8.1.0
Pump kick
5.8.1.1
Pump kick act-
ive/inactive
140
Type Symbol
Values/explanations
Display orientation
±
Display orientation
If delivery head correction is active, the de-
±
viation of the factory-set differential pres-
sure measured by the differential pressure
sensor connected to the pump flange is
taken into account and corrected.
Delivery head correction off
Delivery head correction on (factory set-
ting)
If delivery head correction is active, the de-
±
viation of the factory-set differential pres-
sure measured by the differential pressure
sensor connected to the pump flange and
the different flange diameters are taken
into account and corrected.
Delivery head correction off
Delivery head correction on (factory set-
ting)
HIGH
High switching frequency (factory setting)
MID
Medium switching frequency
LOW
Low switching frequency
Setting for behaviour of signals
±
SBM run signal
SBM standby signal
SBM mains on signal
OFF (default setting) Settings are not
±
changed when confirmed.
ON Settings are reset to factory setting
when confirmed.
Caution! All manual settings will be lost
ON (factory setting)
Pump kick is switched on
Installation and operating instructions • Wilo-Stratos GIGA, Wilo-Stratos GIGA B • Ed.01/2023-05
Display conditions
Only displayed in Δp-c mode. Is not
displayed for all pump variants
Only displayed in Δp-c and Δp-v
mode. Is not displayed for all pump
variants
Carry out the switchover/change
only when the pump is at a standstill
(not when the motor is running)
Is not displayed when access disable
active. Is not displayed when BMS is
active
Is not displayed when access disable
active. Is not displayed when BMS is
active For parameters that are
changed by a factory setting, see
"Factory settings" section.