Pump operation

Installation instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Commissioning
*The configuration of the key lock makes it possible to protect the pump setting from
being changed. This is the case, for example, when the pump is accessed via Bluetooth
or Wilo Net via the Wilo-Smart Connect Gateway with the Wilo-Smart Connect App.
Setting of pump output
The system was designed for a certain duty point (full load point, calculated maximum
heating or cooling power demand). During commissioning, the pump output (delivery
head) is set according to the duty point of the system.
The factory setting does not correspond to the output required for the system. The re-
quired pump capacity is determined with the help of the pump curve diagram for the
selected pump type (e.g. from the data sheet).
NOTICE
For water applications, the flow rate value shown in the display or output to the
building management system applies. For other fluids, this value only reflects the
tendency. If no differential pressure sensor is installed (variant -R1), the pump can-
not indicate a volume flow value.
CAUTION
Risk of material damage!
An inadequate volume flow can lead to damage on the mechanical seal; the min-
imum volume flow depends on the speed of the pump.
• Make sure that the volume flow does not fall below the minimum value Q
Approximate calculation of Q
Q
= 10 % x Q
 x actual speed / max. speed
min
max pump
Settings on pump
Carry out settings by turning and pressing the operating button. Turn the operating
button to the left or right to browse the menus or configure settings. A green focus in-
dicates navigation in the menu. A yellow focus indicates a configuration of settings.
ƒ
Green focus: Navigation in menu.
ƒ
Yellow focus: Change settings.
Set auto control
Settings assistant
Current: Fan heater – Dynamic Adapt ...
Emergency operation speed
Constant speed: 2000/Min
Pump ON/OFF
Current: Motor on
Fig. 29: Green focus: Navigation in menu
:
min
en
.
min
Select a control mode via the
application and
system type.
All control modes
are also available to be selected
directly.