Inhaltsverzeichnis

Werbung

5.1.2 COMBUSTIBLE COMPONENTS

1 cm
2
4
( S )
The minimum clearance required may vary depending on the model
1 A distance of at least 5 cm has to be maintained between furniture (e.g., a wardrobe) and the fireplace
cladding.
2 A clearance of at least 1 cm is recommended for components with small contact areas (wall, floor or
ceiling cladding) .
3 A clearance of at least 80 cm must be maintained between the front and top as well as to the sides of
the combustion chamber opening and all flammable fixtures, fittings as well as built-in furniture, unless
stated otherwise in component-specific safety instructions.
4. A reduced minimum clearance of 40 cm is allowable where ventilated radiant heat protection facilities
(S) are provided on both sides. The ventilated distance to the radiant heat protecting device (S) must
be at least 2 cm.
5 cm
1
3
GB 13
1 cm
( S )
2
3
The minimum clearance required may vary depending on the model
2 A clearance of at least 1 cm is recommended for components with small contact areas (wall, floor or
ceiling cladding) .
3 A clearance of at least 80 cm must be maintained between the front and top as well as to the sides of
the combustion chamber opening and all flammable fixtures, fittings as well as built-in furniture, unless
stated otherwise in component-specific safety instructions.
4. A reduced minimum clearance of 40 cm is allowable where ventilated radiant heat protection facilities
(S) are provided on both sides. The ventilated distance to the radiant heat protecting device (S) must
be at least 2 cm.