1.3 ASSEMBLY SEQUENCE

1. For fireplace inser ts with a ver tical sliding door, first unscrew the
transport safety screws which hold the counter weights!
2. If required, use the clamp or the one-hand clamping lock to attach the
external combustion air swivel to the adapter in the desired position.
3. The fireplace insert has to stand absolutely level!
4. Horizontal connection to the chimney is possible by rotating the flue
gas dome. To do this, open the clamp, put the flue gas dome in position
and clamp it in place again.
2. BASIC REQUIREMENTS FOR SETTING
UP A FIREPLACE SYSTEM
Before installing the fireplace insert, make sure that the air controls func-
tion perfectly and repair if necessary. Consult a local expert to establish
the condition of the chimney and combustion air intake before beginning
installation. Note and apply DIN 18160 and DIN 18896. The responsible
standard DIN EN 13229 must be used. Every fireplace system requires
its own chimney. Multiple allocation is only permitted for fireplaces with
closing loading door.
In the use of an outer chimney systems, especially when using double
stainless steel chimney systems, we recommend the use of an approved
draft limiters.
The chimney calculation is based on DIN 4705 T1, T2 or EN 13384-1 with
the value triplet specified in these instructions. The optionally available
convection jacket is not required for tiled fireplaces. The fireplace system
must be set up as per the professional tiled stoves and ventilation engineer
regulations ( TROL-Richtlinien für den Bau von Kachelöfen, available from
the German Central Association for Sanitation, Heating, and Air Condition-
ing (Z VSHK ), Rathausallee 5, 53729 St. Augustin, Germany).
3. SETUP AND COMBUSTION AIR
SUPPLY

3.1 LOCATION OF THE FIREPLACE

Fireplace systems may only be installed in rooms and places in which the
location, construction situation and type of use do not lead to hazards. In
particular, when the model is dependant on indoor air, sufficient combus-
tion air must flow into the room in which the fireplace is set up. The floor
area must be of sufficient size and of a suitable design to allow an open
fireplace to be used correctly.
3.2 THE OPERATION OF THE FIREPLACE SYSTEM IS
NOT AT DANGER IF
• the chimney system has integrated safety equipment that automatically
and reliably prevents the negative pressure in the installation room.
• the required combustion air volume flow and the volume flow of the
ventilation system as a whole do not require any greater negative pres-
sures than 0.04 mbar in the installation room and the room and the
rooms of the ventilation network.