6.9 Alarm forwarding
Alarm forwarding can take place in two di-
rections, with the following forwarding times:
Alarm forwarding within a
radio group or a shared radio
group = approx. 20 seconds
Alarm forwarding from a
radio group to shared radio
group = approx. 60 seconds
There is no alarm forwarding from the
shared radio group to the individual
radio groups.

Repeater function

Through the repeater function, radio sig-
nals are forwarded from one signalling
device through available devices to un-
reachable devices.
If you need specific, complex and,
where applicable, cascading connec-
tion functions for the alarm forward-
ing, please contact the manufacturer
(see chapter 10 "Accessories, spare
parts and service" on page 77)
70
Operating Manual: PX-1C - Smoke Alarm Device with Radio Link

6.10 Alarm stop

You can stop an alarm with or without fire.
If there is still a risk of fire after
an alarm stop, the switched-off
devices ring again after 10 minutes.
Alarm forwarding has not yet taken place
If the alarm forwarding has not yet taken
place, you can stop the alarm directly on
the alarm-triggering device:
f Press the testing / stop button on
the device triggering the alarm.
5 Alarm is stopped and is not forwarded.
Alarm forwarding has already taken place
If the alarm forwarding has already taken
place in a radio group, and you can iden-
tify the alarm-triggering device, proceed
as follows:
f Press the testing / stop button on
the device triggering the alarm.
5 Alarm on the triggering device and
forwarding devices is stopped.