Object directory
Standardised device profile area, index 2000 to 5FFF
Index
S-idx
6000
0
Resolution
6010
0
Slope Long 16
6011
0
Slope Long 16
Operating
Parameter
6012
0
Slope Long 16
Preset Value
6013
0
Slope Long 16
Name
Type
u16, rw
s16, ro
u8, rw
s16, rw
s16, ro
Offset
Default
Description
0d100
Display resolution of the inclination for
1)
both axes
100 = Inclination is indicated as
signed int in 0.1°
500 = Inclination is indicated as
signed int in 0.5°
1000 = Inclination is indicated as
signed int in 1.0°
Note:
If the display resolution is changed all
offset values or zero point values which
may have been entered are deleted.
Therefore the sensor must be set before
it is aligned!
-
Inclination of the longitudinal axis
(long; X)
Inverting the sign
0b000000xx
0b 0000 00x0
0b 0000 00x1
Scaling of the measured value
0b 0000 000x
0b 0000 001x
Value output:
Slope Long 16 =
measured value in dependence of
Resolution (Index 6000)
+ Slope Long 16 Offset
+ Differential Slope Long 16 Offset
-
Corrects the measured sensor value.
The displayed value Slope Long 16 is set
to the entered value.
The offset is indicated in the index 6013.
(See parameter setting and alignment
of the sensor, page 37)
0x00
Offset value calculated from the
following objects:
Slope Long 16 Offset =
Slope Long 16 Preset Value t
– measured sensor value t
(t
: Instant when the slope Long 16
acc
Preset Value is set)
(See parameter setting and alignment
of the sensor, page 37)
1)
A change of the display resolution
in Idx 6000 is only accepted,
if the scaling in Idx 6011 and Idx 6021
is activated.
CR2102
INCLINATION SENSOR
deactivated
activated
deactivated
1)
activated
acc
acc
PAGE