4.3 Transport
The devices must be transported under clean and dry conditions, if possible in their original pack-
aging. The transport temperature must be between –25 °C and +70 °C. Permissible variations in
temperature may not exceed 20 K per hour.
4.4 Storage
The devices must be stored in clean and dry rooms, if possible in their original packaging. The
storage temperature must be between –25 °C and +55 °C. Permissible variations in temperature
may not exceed 20 K per hour.
Note:
4.5 Mounting the StecaGrid 20000 3ph and 23000 3ph
Mount the inverter by means of the self-centering wall-mounting plate which is included in the
scope of delivery.
Figure No. 8
18
The device contains electrolyte capacitors which can be stored for no
more than 2 years and at a storage temperature of 40 °C while they are
in a de-energized state.
If the storage time of 1 year has been exceeded, please contact the Steca
Service before connecting the device to your system!
Mounting the inverter
748.508 | Z01 | 2013-06-10