Owing to its protection type (IP65), the device can also be mounted in outside areas.
Note:
Note:
To allow for the heat dissipation required, keep the following minimum distances from
the ceiling and wall as well as from neighbouring devices.
Minimum
At the
sides
distances
Figure No. 7
Inverters should in no case be mounted on top of each other without a
Power Cap otherwise the convection cooling will be affected!
CAUTION
748.508 | Z01 | 2013-06-10
To ensure protection class IP65, only use the male and female connectors
provided for connecting the inverter and connect them according to the
connector manufacturer's mounting instructions. To protect against
penetrating moisture and dirt, unused inputs and outputs must be properly
closed. Failure to observe these specifications could void your warranty!
Do not cover the cooling ribs of the heat sink. Failure to observe this
specification could void your warranty.
50 mm
or
1.9685 inches
Minimum distances
At the
500 mm or
top
19.685 inches
EN
At the
500 mm
or
bottom
19.685 inches
17