TMT162
®
Available in ReadWin
2000, HART
Commuwin II with Matrix address
Function mode
Selection of device function
• One sensor input
• Two sensor inputs
Note! Selection only active on two sensor input device.
PV mode
For selecting the calculation function of the PV (PV = primary value). The PV is
shown linear at the analog output.
• PV = Sens1
Sensor 1 is the primary value (PV)
• PV = Sens2
Sensor 2 is the primary value (PV)
• PV = Sens1-Sens2
Difference
• PV = (Sens1 + Sens2)/2
Average of sensor 1 and 2
• PV = Sens1 (or Sens2) backup
Sensor 2 becomes PV if sensor 1 fails. An error signal is not output. If the
active backup = switch to redundant sensor, the display shows the "Caution"
icon, the corresponding error number (see chapter 9) and the text 'back'.
• PV = Sens2 (or Sens1) backup
Sensor 1 becomes PV if sensor 2 fails.
• PV = Sens1 (Sens2, if Sens1 > T)
If temperature T is overshot at sensor 1, the measuring temperature of sensor
2 becomes the PV. The system switches back to sensor 1 if the measuring
temperature at sensor 1 is at least 3.6 °F (2 °C) below T. S1 or S2 appears on
the display to indicate which sensor is currently active. The temperature-
dependent switchover means that 2 sensors can be combined, which each
have certain advantages in different temperature ranges.
Note! Selection only active on "Function - Two sensor inputs".
Temperature T
Switch to sensor 2
Entry only relevant if PV mode is 'PV = Sens1 (Sens2, if Sens1 > T)'
Note! Selection only active on "Function - Two sensor inputs".
PV unit
Input for PV unit
Input: °C, F, K, R, mV or Ω
Note! The setting PV unit has priority, the selection list of the sensor type is
shown independently from the PV unit.
Endress+Hauser
6.4

Device configuration

6.4.1
Description of device functions
All parameters that can be read out and setup for the configuration of the temperature transmitter
are listed and described in the following tables. The menu structures in the ReadWin
configuration software and in the HART
following tables.
Factory default setup is shown in bold text.
Function group STANDARD SETTINGS
®
handheld module DXR275/375 (Symbol
The sensor inputs (≥ SW 01.03.00) are no longer available in the Commuwin II PC
configuration software.
®
handheld module DXR275/375 are shown in the
7
®
),
ReadWin
2000
+
+
≥ SW 01.03.00
≥ SW 01.03.00
≥ SW 01.03.00
≥ SW 01.03.00
+
Commissioning
®
2000 PC
7
/FieldCare
CW II-
Matrix
+
V1H1
+
V1H2
≥ SW 01.03.00
-
≥ SW 01.03.00
-
≥ SW 01.03.00
-
≥ SW 01.03.00
-
+
V1H3