TMT162
®
Available in ReadWin
2000, HART
Commuwin II with Matrix address
Function mode
Selection of device function
• One sensor input
• Two sensor inputs
Note! Selection only active on two sensor input device.
PV mode
For selecting the calculation function of the PV (PV = primary value). The
PV is shown linear at the analog output.
• PV = Sens1
Sensor 1 is the primary value (PV)
• PV = Sens2
Sensor 2 is the primary value (PV)
• PV = Sens1-Sens2
Difference
• PV = (Sens1 + Sens2)/2
Average of sensor 1 and 2
• PV = Sens1 (or Sens2) backup
Sensor 2 becomes PV if sensor 1 fails. An error signal is not output. If the
active backup = switch to redundant sensor, the display shows the
"Caution" icon, the corresponding error number (see chapter 9) and the
text ' b ack' .
• PV = Sens2 (or Sens1) backup
Sensor 1 becomes PV if sensor 2 fails.
• PV = Sens1 (Sens2, if Sens1 > T)
If temperature T is overshot at sensor 1, the measuring temperature of
sensor 2 becomes the PV. The system switches back to sensor 1 if the
measuring temperature at sensor 1 is at least 3.6 °F (2 °C) below T. S1 or
S2 appears on the display to indicate which sensor is currently active.
The temperature-dependent switchover means that 2 sensors can be
combined, which each have certain advantages in different temperature
ranges.
Note! Selection only active on "Function - Two sensor inputs".
Temperature T
Switch to sensor 2
Entry only relevant if PV mode is ' P V = Sens1 (Sens2, if Sens1 > T)'
Note! Selection only active on "Function - Two sensor inputs".
PV unit
Input for PV unit
Input: °C, F, K, R, mV or 
Note! The setting PV unit has priority, the selection list of the sensor type is
shown independently from the PV unit.
Endress+Hauser
6.4

Device configuration

6.4.1

Description of device functions

All parameters that can be read out and setup for the configuration of the temperature
transmitter are listed and described in the following tables. The menu structures in the
®
ReadWin
2000 PC configuration software and in the HART
375 are shown in the following tables.
Factory default setup is shown in bold text.
Function group STANDARD SETTINGS
®
handheld module DXR275/375,
The sensor inputs ( SW 01.03.00) are no longer available in the Commuwin II PC
configuration software.
®
handheld module DXR275/
®
ReadWin
2000
DXR275/375,
FieldCare
+
+
+
+
 SW 01.03.00
 SW 01.03.00
 SW 01.03.00
 SW 01.03.00
 SW 01.03.00
 SW 01.03.00
 SW 01.03.00
 SW 01.03.00
+
+
Commissioning
CW II-
Matrix
V1H1
V1H2
-
-
-
-
V1H3
75