Herunterladen Inhalt Inhalt Diese Seite drucken

Shielding And Potential Equalization - Endress+Hauser iTEMP HART TMT162 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für iTEMP HART TMT162:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Wiring
66
Connection using the Endress+Hauser power supply RN221N
®
HART
connection with the Endress+Hauser power supply RN221N
Connection using other power supplies
®
HART
connection using other power supplies
4.4

Shielding and potential equalization

Please take note when installing the device:
If screened (shielded) cables are used then the shielding connected to the output (output signal 4 to
20 mA) must be at the same potential as the shielding at the sensor connection!
When operating in plants with high electromagnetic fields, it is recommended that all cables be
shielded using a low ohm ground connection. Due to the possible danger of lightning strikes,
shielding is also recommended for cables that are run outside buildings!
TMT162
T09-TMT162ZZ-04-00-XX-xx-003
T09-TMT162ZZ-04-00-XX-xx-002
Endress+Hauser

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis