8.2
Mounting the inverter
Fasten the mounting plate
1
For Australia only: Mask off the Protection Class II symbol on the type plate
Note
When the inverter is used in Australia, the national regulations do not permit the Protection Class II
symbol to be displayed on the type plate. The inverter is therefore supplied with a small sticker in
the same bag as the AC power plug.
Completely cover the Protection Class II symbol using the small sticker provided, as shown
in Fig. 7.
Manufacturer:
Model: StecaGrid 4200
Art. number: 745.282
DC Input:
Voltage: 350 - 845V
MPP Voltage: 350 - 700V
Current: max. 10A
Fig. 7:
Position of the sticker for covering the Protection Class II symbol
Mounting the inverter on the mounting plate
746.217 | 12.27
Screw the mounting plate to the mounting surface using 4
screws:
Use screws (and dowels etc.) appropriate for the weight of
–
the inverter.
The mounting plate must lie flat on the mounting surface
–
and the metal strips at the sides must point forwards (Fig.
left).
Install the mounting plate vertically with the retaining plate
–
at the top (Fig. left).
Note
More information on determining the optimum position for the
mounting plate is provided in the attached information sheet.
The information sheet can also be found on P. 133.
2
Made in Germany
AC Output:
Voltage: 230V, 50/60Hz
Power Factor: 0,95 - 1,0
Current: max. 18,5A
Power: max. 4200W
IP classification: IP 21
Overvoltage category: III
According to:
VDE 0126-1-1:A1,
VDE AR N 4105
1. Grasp the inverter by the recesses , position it in the mid-
1
dle of the mounting plate and press lightly (Fig. left).
2. Lower the inverter into place :
2
The hooks on the rear side of the inverter slide over match-
–
ing protrusions on the mounting plate.
The retaining plate on the mounting plate clicks audibly
3
–
into place.
3. The inverter must now sit securely on the mounting plate and
can no longer be slid upwards.
1
Note
The procedure for removing the inverter from the mounting plate
is described in 8.9, P. 72.
1
1
EN