UL-KENNZEICHNUNG
• WARNING – The opening of the branch circuit protective device may be an indica-
Devices 12, 13 / 480V – housing 4 have been evaluated for connecting to DC voltage,
supplied by other KEB inverters to a DC bus capacitance as follows:
Branch Circuit Protection for series S6 housing size 4
I) Class CC or J, fuses; not more than 5000 rms Symmetrical Amperes (SCCR 5kA);
Class CC, fuses; not more than 30000 rms Symmetrical Amperes (SCCR 30kA):
The voltage rating of the external fuses shall be at least equal to the input voltage of the
drives.
tion that a fault current has been interrupted. To reduce the risk of fire or electrical
shock, current-carrying parts and other components of the controller should be ex-
amined and replaced if damaged. If burnout of the current element of an overload
relay occurs, the complete overload relay must be replaced."
And
ATTENTION – LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU
CIRCUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE
D'UN COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE
CHOC ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET
LES AUTRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT
ENDOMMAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE
COURANT DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT
ÊTRE REMPLACÉ.
Cat. No.
Housing
13S6
04
Cat. No.
Housing
13S6
04
Cat. No.
Housing
12S6
04
13S6
04
14S6
04
Min. capacitance
560uF
DC voltage
680 V
Input Voltage [Vac]
200-230V / 3ph
480 / 3ph
200-230V / 3ph
480 / 3ph
200-230V / 3ph
480 / 3ph
Max. capacitance
18600 uF
Full Load Current
8 A
maximum Fuse size [A]
15
20
25