Delta SOLIVIA 11 EU G4 TR Betriebsanleitung Seite 33

Vorschau ausblenden Andere Handbücher für SOLIVIA 11 EU G4 TR:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Configurable parameters
Display text
Designation
Crit. Umin
Undervoltage
protection U<<
Fmax
Frequency
increase protec-
tion f>
Fmin
Underfrequency
protection f>
tUmin
Delay for U<
9.
Select Continue and press the E
P D D s e t t i n g s
P D D :
S t a n d a r d
C o n t i n u e
- - - - - - - - - - - - - - - - - - -
→ The DC settings menu is displayed. This set-
ting cannot be changed because this solar power
inverter only has a single MPP tracker.
10. Select Continue and press the E
D C s e t t i n g s
M P P T :
C o n t i n u e
- - - - - - - - - - - - - - - - - - -
→ The Locked power limit menu is displayed.
11. If necessary, define power limits.
L o c k e d p o w e r l i m i t
- - - - - - - - -
- - - - - - - - - -
P m a x :
1 1 . 5 k W
S m a x :
1 2 . 0 k V A
Configurable parameters
Display text
Designation
Max. power
Maximum power The maximum power
Smax
Maximum appar-
ent power
NOTE
► If you set a power limit then you
must also fill out the label stating
"The power of the product has been
reduced ..." and apply this label to
the front of the solar power inverter.
Use a waterproof pen for filling out
this information.
12. Select Continue and press the E
→ The Format menu is displayed.
Operation and installation manual for SOLIVIA 11 EU G4 TR
Configurable
Recom-
values
mended by
MVD
0.10 ... 1.00 V
0.45 V
n
ns
50.0 ... 52.0 Hz 51.5 Hz
47.5 ... 50 Hz
47.5
1.5 ... 2.4 s
1.5 ... 2.4 s
button.
ntEr
button.
ntEr
P V 1
Description
that can be fed into the
grid. The value is set
in W.
The maximum apparent
power that can be fed
into the grid. The value
is set in VA.
button.
ntEr
13. Define the date and time formats.
F o r m a t
- - - - - - - - -
- - - - - - - - - -
D a t e :
D D . M M . Y Y Y Y
T i m e :
Configurable parameters
Display text
Designation
Date
Date format
Time
Time format
14. Select Continue and press the E
F o r m a t
T i m e :
C o n t i n u e
- - - - - - - - - - - - - - - - - - -
→ The Date and time menu is displayed.
15. Set the date and time.
D a t e a n d t i m e
- - - - - - - - -
- - - - - - - - - -
D a t e :
1 2 . 0 3 . 2 0 1 2
T i m e :
1 0 : 1 4 : 2 3
16. Select Continue and press the E
D a t e a n d t i m e
T i m e :
1 0 : 1 4 : 2 3
C o n t i n u e
- - - - - - - - - - - - - - - - - - -
→ The RS485 menu is displayed.
17. Set the RS485 ID and the baud rate. Switch on the
termination resistor if required.
R S 4 8 5
- - - - - - - -
- - - - - - - - - - -
I D :
B a u d r a t e :
1 9 2 0 0
Configurable parameters
Display text
Designation
ID
RS485 ID
Baudrate
Baud rate
Termination:
Termination resis-
tor
8. Commissioning
1 2 h
Description
DD.MM.YYYY
DD/MM/YYYY
DD-MM-YYYY
MM.DD.YYYY
MM/DD/YYYY
MM-DD-YYYY
YYYY.MM.DD
YYYY/MM/DD
YYYY-MM-DD
12h | 24h
button.
ntEr
2 4 h
button.
ntEr
1
Description
1 .. 255
2400 | 4800 | 9600 |
19200 | 38400, the
standard is 19200
ON | OFF
EN
29