Identifying code
Description
GO
Motor running
SB
Motor stopped
DIS
Motor status manually disabled
FAULT
Presence of an error preventing operation of the electropump
WARNING
Indicates an Alarm that does not prevent operation of the electric pump.
The other menu pages vary with the associated functions and are described later by type of indication or setting. Once you have entered any
menu, the bottom of the page always shows a summary of the main operating parameters (running status or any fault, current speed and pressure).
This allows a constant view of the machine's fundamental parameters.
Pages showing parameters can display: numerical values and units of measure of the current item, values of other parameters linked to the setting
of the current item, graphic bar, lists; see Fig.16.

4.5 - Blocking parameter setting by Password

The device has a password-enabled protection system. If a password is set, the parameters of the device will be accessible and visible but it will not be
possible to change them. The password management system is in the "technical assistance" menu and is managed by means of the parameter PW.

4.6 - Enabling and disabling the motor

In normal operating conditions, pressing and then releasing both the "˄" and "˅" keys causes the blocking/release of the motor (self-holding even after
switching off). If there is a fault alarm, the operation described above resets the alarm. When the motor is disabled this status is shown by the blinking
white LED. This command can be activated from any menu page except RF and PW.

5. MEANING OF THE INDIVIDUAL PARAMETERS

The inverter makes the system work at constant pressure. This regulation is appreciated if the hydraulic plant downstream from
the system is suitably sized. Plants made with pipes with too small a section introduce load losses that the equipment cannot
compensate; the result is that the pressure is constant on the sensors but not on the utility.
Plants that are excessively deformable can create the onset of oscillations; if this occurs, the problem can be solved by adjusting
the control parameters "GP" and "GI" (see par 5.6.3 - GP: Proportional gain coefficient and 5.6.4 - GI: Integral gain coefficient)

5.1 User Menu

From the main menu, pressing the MODE key (or using the selection menu and pressing ˄ o ˅ ), gives access to the USER MENU. In the menu
the MODE key allows you to scroll through the various menu pages. The values shown are the following.
5.1.1 – Status
Displays the pump status.

5.1.2 - RS: Rotation speed display

Motor rotation speed in rpm.
ENGLISH
Power Shower
Float
Sleep Mode
Table 11: Auxiliary Functions Icons
Footer: Indications on the status bar
Table 12: Indications on the status bar
Figure 16: Display of a menu parameter
49